Rackmount VA 20000 User Manual Page 3

  • Download
  • Add to my manuals
  • Print
  • Page
    / 4
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 2
A Complete System - One Part Number
The complete listing of available conguration bundles is listed in the charts at right.
Each of these bundles provides a complete system including the equipment noted in
the description, making specication, ordering, and installation a simple, straightforward
process. System components include:
UPS Control Unit (CU)
System control unit featuring an LCD status display,
connections for communications, battery packs, and
other modules
2U (5/6kVA) or 3U (8/10kVA) rack height module
Battery Pack (BP)
BP192RTXL (5/6kVA) or BP240RTXL (8/10kVA)
external battery pack
Each bundle includes single battery pack standard
Multiple battery packs can be connected via daisy-chain capability for extreme
runtime needs
External Maintenance Bypass Switch (MTBS)
The MTBS is a separate module from the UPS that
allows the unit to be taken ofine without removing
connected equipment from utility power
Included as a bundle on “-MB” models or sold separately as an accessory; mountable
to the rack (3U total height), to the UPS control unit, or to the wall
If the UPS experiences an internal fault (battery or hardware-related), the user can
bypass the UPS, providing utility power directly to connected equipment while the
UPS is repaired
Efciently upgrade or expand connected equipment without having to bring down
current infrastructure
Isolation Stepdown Transformer (XFR, 5TF)
Independent module which can “step down” the
208V input voltage to 120VAC output voltage
Available in full UPS capacity (XFR) or 5kVA
capacity (5TF)
All transformer modules come with various NEMA output receptacle congurations for
greater exibility on installation requirements
Isolation hardware ideal for sensitive applications including audio/visual equipment,
scientic, and other critical devices
208 In / 208 Out (240V Optional - see page 2)
208 In / 120/208 Out (240V Optional - see page 2)
Scalability Made Easy
Easily expand as needed - purchase or expand 2 208V units for
paralleled operation
System will automatically: (a) Provide double the base unit capacity
if connected load is more than 50% total capacity (b) Provide N+1
redundancy if connected load is less than 50% total capacity
Parallel congurations can be easily ordered using a single part
number; no extra hardware, cables, or other accessories are required
Installation Versatility
All models can be installed as either
rackmount or stand-alone tower
A rail kit (below) for rackmount installa-
tions and foot brackets for stand-alone
installations is also included standard
Tower mount feet expand to allow
additional modules (both transformers
and battery modules) as needed for
growth
View the full line of Endeavor 5-10kVA products at www.minutemanups.com/endeavor510 3
Connect Load
ED-MTBSUPS & BP 1 UPS & BP 2
Connect Utility
UPS Control
UPS Input/Output
Model No.
Input
Voltage
Output
Voltage
Rack
Height
Bundle Contents
(see desc. at left)
ED5200RTXL 208 208 4U CU, BP
ED6200RTXL 208 208 4U CU, BP
ED8200RTXL 208 208 6U CU, BP
ED10200RTXL 208 208 6U CU, BP
w/ Maintenance Bypass Switch (add 3U if rack mounting MTBS)
ED5200RTXLMB 208 208 4U CU, BP, MTBS
ED6200RTXLMB 208 208 4U CU, BP, MTBS
ED8200RTXLMB 208 208 6U CU, BP, MTBS
ED10200RTXLMB 208 208 6U CU, BP, MTBS
Model No.
Input
Voltage
Output
Voltage
Rack
Height
Bundle Contents
(see desc. at left)
ED5000RTXL 208 120 / 208 6U CU, BP, XFR
ED6000RTXL 208 120 / 208 6U CU, BP, XFR
ED8000RTXL 208 120 / 208 9U CU, BP, XFR
ED10000RTXL 208 120 / 208 9U CU, BP, XFR
w/ Maintenance Bypass Switch (add 3U if rack mounting MTBS)
ED5000RTXLMB 208 120 / 208 6U CU, BP, XFR, MTBS
ED6000RTXLMB 208 120 / 208 6U CU, BP, XFR, MTBS
ED8000RTXLMB 208 120 / 208 9U CU, BP, XFR, MTBS
ED10000RTXLMB 208 120 / 208 9U CU, BP, XFR, MTBS
w/ 5kVA Max Transformer (5TF) & MTBS (add 3U if rack mounting MTBS)
ED8000RTXL5TF 208 120 / 208 8U CU, BP, 5TF
ED10000RTXL5TF
208 120 / 208 8U CU, BP, 5TF
ED8000RTXL5TFMB
208 120 / 208 8U CU, BP, 5TF, MTBS
ED10000RTXL5TFMB
208 120 / 208 8U CU, BP, 5TF, MTBS
Parallel
ED10000RTXLP ED12000RTXLP ED16000RTXLP ED20000RTXLP
VA/Watts 10000/9000 12000/10800 16000/14400 20000/18000
MTBS
Weight 368 369 491 492
5/6kVA 120/208V Output Rear View
All Endeavor bundles include a control unit (top), and battery pack (middle). All 120V
output capable systems (ED(X)000RTXL) also include a transformer (bottom).
1. UPS Control Unit
2. SNMP Option Slot
3. Parallel RS-232 Connections
4. Cooling Fans
5. External Battery Connection
6. Input Circuit Breaker
7. Input/Output Connections
8. External Battery Pack
9. Battery Pack (DC) Circuit Breaker
10. Control Unit/BP Connections
11. Optional 120V Transformer
12. 120V NEMA 5-15/20R Output Receptacles
13. 208V L6-20R Output Receptacle
14. 208V L6-30R Output Receptacle
15. Input Voltage Selection (208/240V)
1
2 3 4
5
6
7
12
11
13 14
15
8
9
10
Page view 2
1 2 3 4

Comments to this Manuals