Rackmount VA 20000 User Manual Page 4

  • Download
  • Add to my manuals
  • Print
  • Page
    / 4
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 3
Minuteman
®
Endeavor 5-10kVA Online Rackmount UPS Specifications
© Copyright 2014, Para Systems, Inc. Product specications are subject to change without notice.
Minuteman and Minuteman Platinum Protection Plan are registered trademarks; SentryHD is a trademark of Para Systems, Inc.
General
Model Number - 208V (240V Opt.) Output
(120V Capable)
ED5200RTXL
(ED5000RTXL)
ED6200RTXL
(ED6000RTXL)
ED8200RTXL
(ED8000RTXL)
ED10200RTXL
(ED10000RTXL)
Maximum Power Capacity
5000VA / 4500W
(4556VA / 4100W)
6000VA / 5400W
(5556VA / 5000W)
8000VA / 7200W
(6889VA / 6200W)
10000VA / 9000W
(8889VA / 8000W)
Topology Double Conversion Online, True Sine Wave
Input Plug Type
Hardwire / L6-30P/pigtail cord included
(Hardwire / L6-30P/pigtail cord included)
Hardwire Only
(Hardwire Only)
Output Outlet Type
Hardwire Only
(6 - NEMA 5-15/20R, 1 - L6-20R, 1-L6-30R)
Hardwire Only
(8 - NEMA 5-15/20R, 1 - L6-20R, 1 - L6-30R)
Input
Number of Phases Single (1ф 2W + G)
Nominal Voltage 208 (240VAC factory congurable option)
Acceptable Input Voltage 0 - 300VAC
Voltage Range 156 - 280VAC 180 - 280VAC
Power Factor Correction ≥99% at Full Load
Frequency Limits 40 to 70Hz at Full Load
Low Voltage Transfer Point 156/180 resets to Utility Power at 166/190VAC or higher
High Voltage Transfer Point 280VAC resets to Utility Power at 270VAC or lower
Input Protection Resettable Circuit Breaker
Output: Online
Voltage Range 208VAC: 204 - 212VAC (240VAC: 235 - 245VAC)
Voltage Regulation Nominal +/-2%
Frequency Range 50/60Hz, auto selecting, +/-00.1Hz (unless synchronized to utility)
Efciency (Online Mode) >90% (Full Load)
Output: Battery
Waveform Type True Sine Wave
Nominal Voltage Default: 208VAC, User-selectable:220/230/240VAC
Voltage Regulation Nominal +/-2% (until Low Battery warning)
Frequency 50/60Hz, +/-0.1Hz
Voltage T.H.D. ≤2% (Linear Load)
Dynamic Response +/-5% @ 100% Load change in 30ms
Transfer Time 0 ms
Slew Rate ≤1Hz / second
Crest Factor 3 : 1 2.7 : 1
Overload Capacity ≥106% - ≤110% for 10 minutes / ≥111% - ≤125% for 5 minutes / ≥126% - ≤150% for 30 seconds
Battery
System Voltage 192VDC 240VDC
Runtime: Full Load (minutes) 4 3 5 4
Runtime: Half Load (minutes) 12 11 13 12
Surge Protection
Surge Energy Rating 1050J
Surge Current Capability 6500 Amps total
Surge Response Time 1.2µs normal mode; <50µs common mode
Surge voltage let-through (as a percentage of
an applied ANSI C62.41 Cat. B +/-4kV)
<10%
Noise Filter normal and common mode EMI/RFI suppression
Audible Noise at 1m (3 ft.) <60dBA
Environmental
Operating Temperature (max) 0 to +40°C (+32 to +104°F)
Storage Temperature -15 to +50°C (+5 to +122°F)
Operating/Storage Humidity 0 ~ 95% Non-Condensing
Operating Elevation 0 to 2,000m (0 to +6,562 ft.)
Storage Elevation 0 to 15,000m (0 to +49,213 ft.)
Physical
Size - Net - LxWxH
26.0 x 17.3 x 7.0" / 660.0 x 440.0 x 177.5 mm
(26.2" x 17.3" x 10.5" / 665.0 x 440.0 x 266.0 mm)
24.6 x 17.3 x 10.28" / 625 x 440 x 261.2 mm
(25.9" x 17.3" x 15.4" / 659.0 x 440.0 x 391.8 mm)
Weight - Net
115.8 lbs. / 52.5 Kgs.
(198.5 lbs. / 88.0 Kgs.)
181.0 lbs. / 82.1 Kgs.
(339.7 lbs. / 154.1 Kgs.)
Regulatory
Safety and Approvals cTUVus (Conforms to UL1778 4th Edition & CSA 22.2 no. 107.3-05), RoHS 2 , ENERGY STAR
EMC Verication FCC Class B, CE Certied
Warranty • Platinum Protection Three-years parts, labor, and battery (non-prorated); 5-year extended plans available • $200,000
www.minutemanups.com | www.sizemyups.com