Rackmount VA 6000 User Manual Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 6
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
5125FXA
Revision 06/04
Reprint 06/04
WORLDWIDE HEADQUARTERS
8609 Six Forks Road
Raleigh, NC 27615 U.S.A.
Toll Free: 1.800.356.5794
or 919.872.3020
www.powerware.com
CANADA
Ontario: 416.798.0112
EUROPE/MIDDLE EAST/AFRICA
Denmark: 45.3686.7910
Finland: 358.94.52.661
France: 33.1.6012.7400
Germany: 49.7841.666.0
Italy: 39.02.66.04.05.40
Norway: 47.23.03.65.50
Sweden: 46.8.598.940.00
United Kingdom: 44.1753.608.700
ASIA PACIFIC
Australia/NZ: 61.2.9878.5000
China: 86.21.6361.5599
HK/Korea/Taiwan: 852.2745.6682
India: 91.11.2649.9414 to 18
Singapore/SEA: 65.6829.8888
LATIN AMERICA
Argentina: 54.11.4343.6323
Brazil: 55.11.3616.8500
México: 52.55.9171.7777
Powerware
Electrical Input 1000–2200 VA 2400–3000 VA 5000/6000 VA
Nominal Voltage
2
120, 208 and 230 Vac
2
120, 208 and 230 Vac
2
200/208, 220, 230 and 240 Vac
2
Input Voltage Ranges (for low voltage: 77-152 V 160-288
user-selectable voltages) high voltage: 154-288 V
Operating Frequency 50/60 Hz, auto-sensing
Frequency Range 46-54 hz for 50 hz; 56-64 hz for 60 hz
Electrical Output
On Utility Voltage Regulation -10% to +6% of nominal
On Battery
V
oltage Regulation ±5% RMS
Voltage Wave Shape (on battery) sine wave
Output Protection short circuit protection
Battery
Battery Type sealed, lead-acid; maintenance free
Battery Runtime see Battery Run Time table
Battery Replacement hot-swappable internal batteries and external batteries modules
Recharge Time <3 hours to 90% usable capacity
Start-On-Battery allows start of UPS without utility input
General
Electrical Power Module Replcmnt no yes, hot-swap yes, hot-swap
Diagnostics full system self-test on power up
UPS Bypass no bypass internal bypass
Transfer Time 4ms typical, 6ms max
Dimensions and Weights see Model Selection Guide
Overload (normal operation) 110% overload, shutdown after 3 minutes 100-102 % indefinite, 103-112% 2 minutes and
150% overload, shut down 10 cycles > 112% 12 line cycles
Communications
User Interface front control panel
Audible Alarms for various UPS alarm conditions, including: on battery, low battery, overload, UPS fault
Network Transient Protector UL 497 A, in/out jacks RJ45 (high voltage models No
network protection) & RJ11 (low voltage models modem protection)
REPO Port meets NEC code 645-11 intent and UL requirements
Communication Ports see Communications Slot native USB and serial port
Communication Slot RS-232 single serial module (standard) Web/SNMPxHub card factory
options available, see options chart installed; other options also available
Cable 6-foot communications cable included
Power Management Software Powerware Software Suite CD-ROM (bundled with UPS)
Environmental
Safety Certifications UL; cUL; NOM; C-Tick; CE marking UL; cUL; NOM; C-Tick; CE marking
TUV/VDE, GS
EMC Compliance FCC Part 15, EN50091-2, Class A FCC Part 15, EN50091-2, Class A
for 2.2 KVA and RM; Class B for 1000
and 1500 VA tower models
Operating Temperature 0 to 40ºC (32 to 104ºF) 10°C to 40°C
Storage Temperature -15 to 50ºC (5 to 122ºF) -25°C to 55°C
Relative Humidity 0% to 95% non-condensing
Lightning & Surge Protection ANSI/IEEE C62.41 (IEEE 587), IEC61000-4-5
Surge Energy Rating high-energy 6500 A peak
Audible Noise less than 40 dBA typical less than 45 dBA typical
Altitude 3000m (10,000 ft) without derating
1. Specifications are subject to change without notice due to continuing product improvement programs. 2. See Model Selection Guide for user-selectable voltages.
Technical Specifications
1
Powerware
®
, ABM
®
technology and PowerVision
®
are registered trademarks of Powerware Corporation©2004. IBM
®
and eServer
®
are trademarks of IBM Corporation.