OPERATION
Eaton 5125 Rack-Mount UPS (5000/6000 VA) User's Guide S 164201541 Rev D
www.eaton.com/powerquality
42
Battery Mode
When the UPS is operating during a power outage, the alarm beeps
intermittently, the
+
-
indicator illuminates, and the
indicator
flashes.
When utility power returns, the UPS transfers to Normal mode operation
while the battery recharges.
If battery capacity becomes low while in Battery mode, the
+
-
indicator
starts flashing and the alarm becomes continuous. Immediately
complete and save your work to prevent data loss and similar difficulties.
When utility power is restored after the UPS shuts down, the UPS
automatically restarts. The
indicator flashes until the battery has
recharged to an acceptable level.
Bypass Mode
In the event of a UPS overload or internal failure, the UPS transfers your
equipment to utility power. Battery mode is not available; however, the
utility power continues to be passively filtered by the UPS. The alarm
sounds and the
indicator illuminates red. The UPS transfers to
Bypass mode when:
S The UPS has an overtemperature condition.
S The UPS has an overload condition of 102 to 110% for 2 minutes.
S The UPS has an overload condition >110% for 12 cycles.
S The UPS detects a fault in the UPS electronics.
Standby Mode
When the UPS is turned off and remains connected to utility power, the
UPS is in Standby mode. The
indicator flashes and the load level
indicators are off, indicating that power is not available to your
equipment. The battery recharges when necessary.
NOTE For 200–240V models, the output receptacles may remain electrically live (up to
100–120V). Unplug the UPS to ensure power is not available to the output receptacles.