Table 7. Environmental and Safety
PW5125 5000 PW5125 6000i PW5125 6000 HW
Operating
Temperature
10°C to 40°C (50°F to 104°F)
Optimal battery performance: 25°C (77°F)
Storage Temperature 0°C to 25°C (32°F to 77°F)
Transit Temperature -25°C to 55°C (-13°F to 131°F)
Relative Humidity 5–95% noncondensing
Operating Altitude Up to 2,000 meters above sea level
Transit Altitude Up to 15,000 meters above sea level
Audible Noise Less than 45 dBA Normal mode, typical load
Less than 50 dBA Battery mode
Surge Suppression ANSI C62.41 Category B3
EN 61000-4-5 Level 3, Criteria B
Safety Conformance UL 1778, CSA C22.2, No. 107.3;
IEC 62040-1-1 and IEC 60950-1
Agency Markings cULus, cUL GS, CE, GOST
EMC (Class A) IEC 62040-2, FCC Part 15,
ICES-003, VCCI
IEC 62040-2, FCC Part 15, ICES-003
Table 8. Battery
UPS Configuration (20) 12V, 7.2 Ah internal batteries
EBM Configuration EBM 240: (20) 12V, 9 Ah
Type Sealed, maintenance‐free, valve‐regulated, lead‐acid
Charging Internal battery: approximately 3 hours to 80% usable capacity
at nominal line voltage after full load discharge
External battery: no more than 15x discharge time to 90% usable capacity
at nominal line voltage after full load discharge
Monitoring Advanced monitoring for earlier failure detection and warning