ADDITIONAL UPS FEATURES
Eaton 5125 Rack-Mount UPS (5000/6000 VA) User's Guide S 164201541 Rev D
www.eaton.com/powerquality
48
DB-9 Communication Port
To establish communication between the UPS and a computer, connect
your computer to the UPS communication port using the supplied
communication cable.
When the communication cable is installed, power management
software can exchange data with the UPS. The software polls the UPS
for detailed information on the status of the power environment. If a
power emergency occurs, the software initiates the saving of all data
and an orderly shutdown of the equipment.
Figure 23 identifies the cable pins and Table 3 describes the pin
functions.
3
8
7
9
1
6
245
Figure 23. Communication Port
Table 3. Communication Port Pin Assignment
Pin Number Signal Name Function Direction from the UPS
1 Low Batt Low Battery relay contact; 20 mA, 30 Vdc contact rating Out
2 TxD Transmit to external device Out
3 RxD Receive from external device In
4 DTR PnP (Plug and Play) from external device (tied to Pin 6) In
5 GND Signal common (tied to chassis)
6 DSR To external device (tied to Pin 4) Out
7 No Connection
8 AC Fail AC Fail relay contact; 20 mA, 30 Vdc contact rating Out
9 Power Source +V (8 to 24 volts DC power) Out